267 Academy Avenue Pittsburgh, PA 15228

Phone: (412) 561-5050Fax: (412) 561-2242
E-Mail: peco@processengineering.com
 

Conversions and Formulas


E = Voltage / I = Amps / W = Watts / PF = Power Factor / Eff = Efficiency / HP = Horsepower

AC/DC Power Formulas
To Find Direct Current AC / 1phase
115v or 120v
AC / 1phase
208,230, or 240v
AC 3 phase
All Voltages
Amps
(when HP is known)
HP x 746
E x Eff
HP x 746
E x Eff X PF
HP x 746
E x Eff x PF
HP x 746
1.73 x E x Eff x PF
Amps
(when Kilowatts is known)
kW x 1000
E
kW x 1000
E x PF
kW x 1000
E x PF
kW x 1000
1.73 x E x PF
Amps
(when kVA is known)
  kVA x 1000
E
kVA x 1000
E
kVA x 1000
1.73 x E
Kilowatts I x E
1000
I x E x PF
1000
I x E x PF
1000
I x E x 1.73 PF
1000
Kilovolt-Amps (kVA)   I x E
1000
I x E
1000
I x E x 1.73
1000
Horsepower
(output)
I x E x Eff
746
I x E x Eff x PF
746
I x E x Eff x PF
746
I x E x Eff x 1.73 x PF
746


 



Chemical/Gas IDLH Listings
NIOSH Pocket Guide to Chemical Hazards
(3rd Printing with minor technical revisions) [PDF Download 6.192KB]


To find mA for a given pressure in a 4-20 Loop:

ex. 0 - 500 PSI = 4 - 20 mA
Span of mA
Range of Pressure
ie:
16 mA
500 PSI
= .032 mA per PSI
.032 mA X 250 PSI = 8 mA + 4 mA (offset from 0) = 12 mA
or
250 PSI = 12 mA

 


Here are LINKS to a few of the WWW's best Converters & Formula Pages.
On-Line Generic Converter
On-Line Megaconverter
On-Line Metric Converter
Josh Madison's Free Converter Download
a must for every desktop!

eFunda Engineering Formulas
Engineers Edge

 